Summary
FZW32-12/24/40.5 Outdoor AC high voltage disconnect vacuum load break switch is a new product adopts domestic existing mature
load break switch production expe rience and overseas advanced technology to design and manufacture. the load break switch is
composed of disconnect blade, vacuum interrupter and ope~tion mechanism vacuum extinguishing arc, there are merits as strong
extinguishing arc ability, reliable performance, long lifetime, small volume, no explosive danger and no pollution to environment. It
accords with standards of IEC62271-103 High voltage switches.
Ambient conditions
1. Altitude:≤1000m;
2. Ambient temperature:-30℃-+400℃;
3. Wind speed:≤34m/s;
4. POllution degree:≤IV;
5. Earthquake intensity:≤8 degree;
6. lce thickness:≤10mm.
Model
Technical specification
No.
|
Item
|
Unit
|
Data
|
1
|
Rated voltage
|
kV
|
12/24
|
40.5
|
2
|
Rated current
|
A
|
630,1250
|
3
|
Rated power frequency
|
Hz
|
50/60
|
4
|
Rated peak withstand current
|
kA
|
50,63
|
5
|
Rated short-time withstand current
|
kA
|
20,25
|
6
|
Rated short-circuit duration
|
s
|
4
|
7
|
Rated active load breaking current
|
A
|
630,1250
|
8
|
Rated loop breaking current
|
A
|
630,1250
|
9
|
Rated cable charging current
|
A
|
10
|
10
|
5%rated active load breaking current
|
A
|
31.5,63
|
11
|
Rated power transformer breaking current
|
kVA
|
1250
|
12
|
Rated short-circuit making current
|
kA
|
50,63
|
13
|
Main loop resistance
|
μΩ
|
≤90
|
≤100
|
14
|
1min.power frequency
withstand voltage
|
Dry
|
phase to phase phase to earth
|
kV
|
42/50
|
95
|
across open contacts
|
kV
|
49/60
|
115
|
Wet
|
phase to phase phase to earth
|
kV
|
30/40
|
85
|
15
|
Lightning impulse withstand
voltage(peak)
|
phase to phase phase to earth
|
kV
|
75/125
|
185
|
across open contacts
|
kV
|
85/145
|
215
|
16
|
Mechanical life
|
Times
|
10000
|
10000
|
17
|
Three phase closing asynchronous
|
ms
|
≤5
|
≤5
|
18
|
Direction rotating of making contact blade
|
mm
|
≤2
|
≤2
|
19
|
Main contact blade pressure
|
N
|
300±30
|
420±42
|
20
|
Distance between electric Darts and phase to earth
|
mm
|
≥200
|
≥380
|
21
|
Rated operating moment
|
Nm
|
≤300
|
≤300
|
|
LBS with vacuum arc extinguish chamber
No.
|
Item
|
Unit
|
Data
|
1
|
Contact distance
|
mm
|
5±1
|
18±1
|
2
|
Average breaking speed
|
m/s
|
1.1±0.2
|
1.6±0.2
|
3
|
Three phase breaking asynchronous
|
ms
|
≤5
|
≤5
|
4
|
Three phase making asynchronous
|
ms
|
≤5
|
≤5
|
|
Structure feature